FUNCTIONS
6.12 Remote Operation
6.12.2 Remote RESET
6 - 51
1
Overview
2
Performance
Specification
3
Sequence Program
Configuration and
Execution Conditions
4
I/O Nunber Assignment
5
Memories and Files
Handled by CPU Module
6
Functions
7
Communication with
Intelligent Function
Module
8
Parameters
POINT
1. If remote RESET is performed with the CPU module stopping due to an error,
note that the CPU module is placed in the operation status set by the RUN/
STOP/RESET switch upon completion of the reset processing.
2. Remote processing in GX Developer can be completed without setting
Remote reset to "Allow" in the PLC system setting screen of PLC parameter.
However, the reset processing is not performed to the CPU module,
accordingly the CPU module will not be reset.
When the CPU module status does not change with Remote reset in GX
Developer, check if the Remote reset on the "PLC system" setting screen is
set to "Allow".