APPENDICES
Appendix 1 Special Relay List
App - 3
9
Device Explanation
10
CPU Module Processing
Time
11
Procedure for Writing
Program to CPU ModuleAppendices
Index
(2) System information
(3) System clocks/counters
(4) Safety CPU
TableApp.3 Special relay
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
CPU
SM203 STOP contact STOP status Goes ON at STOP status S (Status change)
QS
SM213
Clock data read
request
OFF : Ignored
ON : Read request
When this relay is ON, clock data is read to
SD210 to SD213 as BCD values.
U
SM232
Number of
writes to ROM
OFF : Within the number
of writes
ON : Over the number of
writes
Turns ON when the number of writes to ROM
exceeds 100,000.
S (Error)
TableApp.4 Special relay
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
CPU
SM400 Always ON Normally is ON S (Every END)
QS
SM401 Always OFF Normally is OFF S (Every END)
SM402
After RUN, ON
for 1 scan only
After RUN, ON for 1 scan only. S (Every END)
SM403
After RUN, OFF
for 1 scan only
After RUN, OFF for 1 scan only. S (Every END)
SM410
0.1 second
clock
Repeatedly changes between ON and OFF
at each designated time interval.
When PLC power supply is turned OFF or a
CPU module reset is performed, goes from
OFF to start.
S (Status change)
SM411
0.2 second
clock
SM412 1 second clock
SM413 2 second clock
SM414
2n second
clock
This relay alternates between ON and OFF at
intervals of the time (unit: s) specified in
SD414.
When PLC power supply is turned OFF or a
CPU module reset is performed, goes from
OFF to start.
S (Status change)
TableApp.5 Special relay
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
CPU
SM560
TEST MODE
flag
OFF : Other than TEST
MODE
ON : TEST MODE
Turns ON when operating on the TEST
MODE.
Turns OFF when operating on the other
mode (SAFETY MODE, SAFETY MODE
(wait-for-restart)).
S (Status change)
QS
SM561
Continuous
RUN of
tolerance time
setting for the
TEST MODE
OFF : Within the setting
time
ON : Over the setting
time
Turns ON when the continuous RUN of
tolerance time set for the TEST MODE in the
parameter is exceeded.
S (Error)
ON
OFF
ON
OFF
ON
OFF
1 scan
ON
OFF
1 scan
0.05s
0.05s
0.1s
0.1s
0.5s
0.5s
1s
1s
ns
ns