Appendix 1 Special Relay List
APPENDICES
(1) Diagnostic Information
TableApp.2 Descriptions of the special relay headings
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
CPU
SM0
Diagnostic
errors
OFF : No error
ON : Error
Turns ON when an error is detected by
diagnostics
(Includes when an annunciator is ON)
Remains ON if the condition is restored to
normal thereafter.
S (Error)
QS
SM1
Self-diagnosis
error
OFF : No self-diagnosis
errors
ON : Self-diagnosis
Turns ON when an error is detected by self-
diagnostics
(Does not include when an annunciator is
ON)
Remains ON if the condition is restored to
normal thereafter.
S (Error)
SM5
Error common
information
OFF : No error common
information
ON : Error common
information
When SM0 is ON, ON if there is error
common information
S (Error)
SM16
Error individual
information
OFF : No error individual
information
ON : Error individual
information
When SM0 is ON, ON if there is error
individual information
S (Error)
SM50
Error reset OFF ON: Error reset Conducts error reset operation U
SM51
Battery low
latch
OFF : Normal
ON : Battery low
ON if battery voltage at CPU module or
memory card drops below rated value.
Remains ON if the battery voltage returns to
normal thereafter.
Synchronous with BAT. LED
S (Error)
SM52
Battery low
OFF : Normal
ON : Battery low
Same as SM51, but goes OFF subsequently
when battery voltage returns to normal.
S (Error)
SM53
AC DOWN
detection
OFF : AC DOWN not
detected
ON : AC DOWN
detected
Turns ON if an instantaneous power failure of
within 20ms occurs during use of the AC
power supply module.
Reset when the power supply is switched
OFF, then ON.
S (Error)
SM56
Operation error
OFF : Normal
ON : Operation error
ON when operation error is generated
Remains ON if the condition is restored to
normal thereafter.
S (Error)
SM61
I/O module
verify error
OFF : Normal
ON : Error
Turns ON if the I/O module differs from the
status registered at power on.
Remains ON if the condition is restored to
normal thereafter.
S (Error)
SM62
Annunciator
detection
OFF : Not detected
ON : Detected
Goes ON if even one annunciator F goes ON.
S (Instruction
execution)