Back to Basics SM600 Bedienungsanleitung Seite 109

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 234
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 108
6
FUNCTIONS
6.7 Self-diagnostics Function
6 - 29
1
Overview
2
Performance
Specification
3
Sequence Program
Configuration and
Execution Conditions
4
I/O Nunber Assignment
5
Memories and Files
Handled by CPU Module
6
Functions
7
Communication with
Intelligent Function
Module
8
Parameters
(6) Self-diagnostics list
Here is a list of the self-diagnostics executed by the CPU module.
The error messages in the "Error message" column in Table6.11 can be checked
using GX Developer [Diagnostics] [PLC Diagnostics].
(Continued to the next page)
Table6.11 Self-diagnostics list
No.
Detailed item/
Diagnostics subject
Diagnostics description
Diagnostics
timing
Error occurring when error is detected
Error code Error message
1 RAM diagnostics Is the CPU module internal memory destroyed?
When power-on
When reset
canceled
1131,1132,1133,
1136,1137
RAM ERROR
Always
1141,1142,1143,
1146
2 F/W diagnostics Is F/W stored in ROM corrupted?
When power-on
When reset
canceled
When an END
instruction executed
8060 INCORRECT FIRMWARE
3
Operation circuit
diagnostics
Are the operation circuits for sequential
processing in the CPU module working
correctly?
When power-on
When reset
canceled
When an END
instruction executed
1210 OPERATION CIRCUIT ERROR
4 Program verify
Are any files stored in program memory
corrupted?
When power-on
When reset
canceled
8031
INCORRECT FILE
When an END
instruction executed
8032
5 Output data verify
Do the operation results that are output from
CPUs A/B match?
When an END
instruction executed
8050
SAFETY OUTPUT VERIFY
ERROR
6 Time monitoring
Do CPUs A/B have the same OS execution
state?
Always 8020
CPU A & B CAN'T BE
SYNCHRONIZED
When an END
instruction executed
8021
7 Microcomputer diagnostics
Are the registers used with the CPU module
working correctly?
When power-on
When reset
canceled
When an END
instruction executed
8000
INTERNAL REGISTER
ERROR
8010 INTERNAL BUS ERROR
8
Power supply voltage
monitoring
Is the safety CPU module operating at a voltage
within the range for which operation is assured?
Always 8080 POWER SUPPLY ERROR
9
Power supply voltage
monitoring circuit
diagnostics
Are the circuits that monitor the power supply
voltage working correctly?
When an END
instruction executed
8090
VOLTAGE DIAGNOSIS
ERROR
10 Clock stop detection
Is input clock to the CPU module internal circuit
stopped?
Always 8120 WDT CLOCK CHECK ERROR
11 CPU module OS
Check that the main CPU is not going out of
control but is operating normally.
Always 1000, 1006 MAIN CPU DOWN
12 CPU module hardware
Is the hardware below for the CPU module
working correctly?
Main CPU
Clock element
RUN/STOP/RESET switch
Always
1001, 1002,
1003, 1004
MAIN CPU DOWN
13 Power supply module Has the power supply module failed? Always 1009 MAIN CPU DOWN
14 Program
Was the END instruction executed at the end of
the user program?
When an END
instruction executed
1010 END NOT EXECUTE
15
CPU module, base unit,
CC-Link Safety master
module, MELSECNET/H
module
Was an invalid interrupt generated within the
CC-Link Safety master module, MELSECNET/
H module, base unit, or CPU module?
During interrupt 1311 I/O INTERRUPT ERROR
16
Module state during
operation
Are the CC-Link Safety master module and
MELSECNET/H module operating normally?
When power-on
When reset
canceled
1401
INTELLIGENT FUNCTION
MODULE DOWN
When an END
instruction executed
1403